City of Gravette (AR)
NEC Code Version2014
Fire Code Version2018 Building Code
Wet Stamps RequiredNone
Fire Setback Enforced1
Codes
- NEC Code Version
- 2014
- Fire Code Version
- 2018 Building Code
- Code List
2012 ARKANSAS FIRE PREVENTION CODE
2017 NATIONAL ELECTRIC CODE
2006 ARKANSAS STATE FUEL GAS CODE
2006 ARKANSAS STATE PLUMBING CODE
2010 ARKANSAS STATE MECHANICAL CODE
2014 ARKANSAS STATE ENERGY CODE
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 1
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- None
- Structural Calculations Required
- No
Fire setbacks
- Fire Setback Enforced
- 1
Structural & loads
- Wind Speed
- 90
- Snow Load
- 10
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Line Side Taps,Load Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- Separate ESS Disconnect Required
- No
- ESS Elevation Detail Required
- No
Ground mount
- Ground Mount Fencing Required
- No
- Setback Front Yard
- 10
- Setback Back Yard
- 5
- Setback Side Yard
- 5