Town of Fountain Hills (AZ)
Codes
- NEC Code Version
- 2017
- Fire Code Version
- 2018 Building Code
- Code List
2018 INTERNATIONAL BUILDING CODE (IBC) 2017 NATIONAL ELECTRICAL CODE (NEC) 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2018 INTERNATIONAL FIRE CODE (IFC) 2018 INTERNATIONAL FUEL GAS CODE (IFGC) 2018 INTERNATIONAL MECHANICAL CODE (IMC) 2018 INTERNATIONAL PLUMBING CODE (IPC) 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) WITH APPENDIX G 2018 UNIFORM SWIMMING POOL, SPA AND HOT TUB CODE 1997 UNIFORM ADMINISTRATIVE CODE 1997 UNIFORM CODE FOR THE ABATEMENT OF DANGEROUS BUILDINGS
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 2
- Revision Required
- 1
- New Planset Required For Module Swap
- 1
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,Line Side Taps,Meter Adapter,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 1
- ESS Notes
Required: Disco and PM between B/U load panel and inverter. Do this on Site Plan and ELD(s): Call out ESS Disco as DER Storage Disconnect . Call out ESS PM as DER Storage Meter . Call out make and model for all Disconnects. Show blades of all Disconnects open to the inverter. No published information about battery placement.
- Separate ESS Disconnect Required
- Local Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
NOTE : PHOTOVOLTAIC EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH NEC 690 AND POSTED WITH APPLICABLE WARNINGS, SIGNAGE AND PLAQUES PER NEC 705-10, 690-17 AND 690-64(B)95).
- Electrical Diagram
SLD & 3LD
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim