City of Berkeley (CA)
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusAdopted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Adopted
- Date SolarAPP+ Accepted
- 45182
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- Existing Systems,Trenching,MPU,Derate
- How Many Plansets Required
- Other (See Submission Notes)
- Revision Required
- 1
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Panels are allowed to be mounted a maximum of 10 inches or less above the roof surface or a licensed engineer is required to provide structural design calculations and details for wind uplift and all connections. [CBC 3111.1.1]
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Meter Adapter,Load Side Taps,Line Side Taps,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 1
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
- ESS on the exterior side of exterior walls shall be located not less than 3 feet from doors and windows directly entering the dwelling unit. [CRC R328.4(3)]
- Provide manufacturer’s installation and mounting specifications
- Include mounting detail of ESS on Elevation page
- Where energy storage device input or output terminals, or the circuits from these terminals pass through a wall, floor or ceiling, a readily accessible disconnecting means and overcurrent device shall be provided within sight of the energy storage component. Fused disconnecting means or circuit breakers shall be permitted to be used. [CEC 706.15 (A)(1)(2)&(D)]
- The disconnecting means shall be legibly marked in the field. The marking shall meet the requirements of CEC 110.21(B) and shall include the following:
- [CEC 706.15(C)] “ENERGY STORAGE SYSTEM DISCONNECT, Nominal ESS AC Voltage, Maximum ESS DC Voltage”
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- Yes
Plan set
- Plan Set Requirements
- Cover Page
- Indicate the existing and proposed Occupancy Group classification(s). [CBC 302.1]
- Indicate each structure’s occupancy type (single family, multifamily, commercial or accessory structure, etc.).
- Provide the number of units, and the number of stories.
- Roof Plan
- Provide specifications for the existing roof framing member size, spacing and span.
- If the existing roof rafter spacing exceeds the maximum allowable under current code, provide plans and construction details for the reinforcement of the roof framing or provide calculations produced by a licensed design professional showing that the existing framing is adequate to support the applicable design loads. [CRC R802.5]
- Attachment Detail
- The sample roof framing plan must be adjusted to match the layout on the roof.
- Include distance from roof to top of module on plans.
- Panels to be maximum of 10 inches above the roof surface
- Electrical Diagram
- Label Page
- Battery jobs required the following label on the disconnect: “ENERGY STORAGE SYSTEM DISCONNECT Nominal ESS AC voltage ___ and maximum ESS DC voltage___”
- Provide an ESS disconnect label with the information listed above
- Custom Placards Required
- 1
Ground mount
- Ground Mount Fencing Required
- No