City of Oxnard (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusAdopted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Adopted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
Existing Systems,Trenching
How Many Plansets Required
3
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
No
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

36" Access pathway from eave to ridge required on all roof plains with solar panels

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category C

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

Standard

Minimum Ground On Roof
#10

Electrical

AC Disconnect Required
Yes
Electrical Load Calcs Required
Derates
Allowed POI
Meter Adapter,PV Breaker,Line Side Taps,Load Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
1
BOS Restrictions

Standard

Battery / ESS

Unique Battery Placards Needed
1
ESS Notes

Provide information on how the ESS will be mounted, including type of screws that will be used. Label required: CAUTION: TRI POWER SOURCE SECOND SOURCE IS AC BATTERY THIRD SOURCE IS PHOTOVOLTAIC SYSTEM Provide elevation drawing demonstrating that ESS will be minimum 3ft from doors, windows, and other ESS.

ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
Yes - with dimensions

Plan set

Plan Set Requirements

* Racking/attachment system installation manual must be included with plans

Cover Page

* Provide a scope of work for the project. AHJ does not have a set template for this, list a basic description of the work being done and materials to be installed. * Vicinity map MUST be black and white line drawing. Follow steps below to generate this: Follow this link: 1\. Style: Under "Style" click "choose a Snazzy maps style". Then type "lines" in the search bar that appears and select the first option. Then hit "apply style". 2\. Size & Location: Click the pencil icon. Under "Center Location", click the green text that states "Or search for a location". Enter the site address. Click "apply changes". 3\. Markers: click on "Add your first marker". Under "Location", click the green text that states "Or search for a location". Enter the site address and hit "apply changes". 4\. Zoom in to the map until only the site and the nearest cross streets are showing. Take a snip of this image to use as the vicinity map. DO NOT use the save image feature from the website. Doing so will cause the site to ask the user to register for an account.

Site

* AHJ wants property lines _but not the dimensions_ please (This AHJ is very picky) * Please show all structures on site plan. If they appear unpermitted AHJ may request this to be labeled.

Site Notes

All Jobs [ **MOUNTING HARDWARE IS TO CONNECT DIRECTLY TO ROOF FRAMING MEMBERS CONNECTIONS WHICH RELY SOLEY ON ROOF SHEATHING ARE NOT ACCEPTABLE]**

Electrical Diagram
  • Centerfed 120% allowed.
  • Service upgrades: SPD required. Call out SPD on line diagram. Identify whether type 1 or type 2. Provide spec sheet for SPD.
Electrical Diagram Notes

All Jobs [In dwelling units where branch-circuit wiring is modified, replaced, or extended in any of the areas specified in 210.12(A) or (B), the branch circuit must be protected by either a listed combination AFCI located at the origin of the branch circuit or a listed branch circuit AFCI located at the first receptacle outlet of the existing branch circuit unless the extension of conductors is 6ft or less and no outlets or devices are added]

Custom Placards Required
1

Ground mount

Ground Mount Fencing Required
Mesh/Scrim
Setback Front Yard
25
Setback Back Yard
25
Setback Side Yard
15
Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the City of Oxnard (CA) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.