City of Torrance (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusTargeted
Wet Stamps RequiredNone
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

IEBC Accepted
1
ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Targeted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,MPU,Derate,Derate
How Many Plansets Required
2
Revision Required
1
New Planset Required For Module Swap
0

Stamps

Wet Stamps Required
None
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes
  • MINIMUM 3' SETBACK REQUIRED ON BOTH SIDES OF THE RIDGE, EVEN IF MODULES ARE ONLY LOCATED ON ONE SIDE OF THE RIDGE.
  • IF MODULES ARE PLACED ON BOTH SIDES OF A RIDGE, 3' IS REQUIRED ON ONE SIDE & 5' IS REQUIRED ON THE OTHER SIDE OF THE RIDGE
  • FLAT ROOFS REQUIRE A 3' PERIMETER SETBACK AROUND ROOF EDGE

Structural & loads

Wind Speed
130
Wind Notes

Exposure Category B

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

Structural calcs must provide wind analysis and uplift calcs

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
All Jobs
Allowed POI
Load Side Taps,PV Breaker,Line Side Taps,Meter Adapter
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
1
BOS Restrictions

Standard

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
Yes - with dimensions

Plan set

Plan Set Requirements


Site
  • The AC disconnect must be located within line of sight and within 10 feet of main electrical service.
  • ESS SHALL BE LOCATED NOT LESS THAN 3 FEET (914MM) FROM DOORS, WINDOWS, AND OTHER OPENINGS DIRECTLY ENTERING THE DWELLING UNIT.
Roof Plan
  • SPECIFY HEIGHT FROM THE ROOF TO THE TOP OF THE PANEL
  • INCLUDE LEADER SHOWING FIRE ACCESS POINT
Roof Plan Notes

All Jobs [PV SOURCE CIRCUIT CONDUCTORS AND PV OUTPUT CIRCUIT CONDUCTORS SHALL BE PROTECTED FROM PHYSICAL DAMAGE WHEN INSTALLING OUTSIDE OF THE ARRAY. ALL CONDUIT RUNS LEADING TO THE ROOF OR ALONG THE ROOF TO BE RMC INSTEAD OF EMT SO THAT THEY SHALL BE PROTECTED FROM PHYSICAL DAMAGE. (E.G. RMC) CEC 690.31 (A) & (B)]

Attachment Detail


Electrical Diagram

AHJ DOES NOT ALLOW EMT (ELECTRICAL METAL TUBING) ONLY RMC (RIGID METAL CONDUIT)

  • ALL REFERENCES TO EMT SHALL BE REMOVED AND REPLACED WITH RMC
Electrical Diagram Notes

All Jobs [PV SOURCE CIRCUIT CONDUCTORS AND PV OUTPUT CIRCUIT CONDUCTORS SHALL BE PROTECTED FROM PHYSICAL DAMAGE WHEN INSTALLING OUTSIDE THE ARRAY. ALL CONDUIT RUNS LEADING TO THE ROOF OR ALONG THE ROOF TO BE RMC INSTEAD OF EMT SO THAT THEY SHALL BE PROTECTED FROM PHYSICAL DAMAGE. (E.G. RMC) CEC 690.31 (A) & (B)]


Battery [ESS SHALL BE LOCATED NOT LESS THAN 3 FEET (914MM) FROM DOORS, WINDOWS, AND OTHER OPENINGS DIRECTLY ENTERING THE DWELLING UNIT.]

Custom Placards Required
1
Non Standard Planset Requirements
BOS Elevation

Ground mount

Ground Mount Fencing Required
No