County of Los Angeles (Covina) (CA)
NEC Code Version2020
Fire Code Version2018 Building Code
Wet Stamps RequiredNone
Fire Setback Enforced1
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
- 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA FIRE CODE 2022 CALIFORNIA PLUMBING CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA ADMINISTRATIVE CODE
- IEBC Accepted
- 1
SolarAPP+ & submittal
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- None
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
- Standard
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 999
- Snow Load Notes
* Elevations between 2000 and 3500 ft. require 20 psf snow load to be accounted for. * Elevations between 3500 and 5000 ft. require 40 psf snow load to be accounted for. * Elevations greater than 5000 ft. require 80 psf snow load to be accounted for. BCM1608 A1
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- SE digital stamps on corresponding pages, PE Letter & Calcs. For ballast mount projects use PZSE (contact ) for structural engineering ### Bus Certs are NOT accepted in this AHJ
- Minimum Ground On Roof
- #8
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,PV Breaker,Meter Adapter,Load Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 75
- De Rating Ampacity
- 0.96
- BOS Restrictions
- Need to show 3' Clearance from gas meter to any new electrical equipment
Battery / ESS
- ESS Notes
[LACOF]
This AHJ follows County of Los Angeles (ESS Requirements) (CA).
Please follow this link to County of Los Angeles (ESS Requirements) (CA)
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Roof Plan
- For systems with multiple strings/inverters, the plans shall clearly identify how all modules are mapped to each string and/or inverter input
- Attachment Detail
- Distance from top of module to roof is to be called out
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim