County of Indian River (FL)
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2023 8TH EDITION FLORIDA BUILDING CODE: BUILDING
2023 8TH EDITION FLORIDA BUILDING CODE: RESIDENTIAL
2023 8TH EDITION FLORIDA BUILDING CODE: MECHANICAL
2023 8TH EDITION FLORIDA BUILDING CODE: PLUMBING
2023 8TH EDITION FLORIDA BUILDING CODE: FUEL GAS
2023 8TH EDITION FLORIDA BUILDING CODE: ENERGY CONSERVATION
2023 8TH EDITION FLORIDA BUILDING CODE: EXISTING BUILDING
2023 8TH EDITION FLORIDA BUILDING CODE: ACCESSIBILITY
2023 8TH EDITION FLORIDA FIRE PREVENTION CODE (NFPA)
2020 NATIONAL ELECTRIC CODE (NEC)
- ASCE Code Specification
- ASCE 7-22
SolarAPP+ & submittal
- Revision Required
- 1
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes
- Wet Stamps Required
- Digital Structural,Digital Electrical
- Structural Calculations Required
- Yes
- Ee Stamp Notes
Digitally Verified Signature
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Provide Roof access and pathways complying with the parameters in FBC R324.6
Structural & loads
- Wind Speed
- 160
- Wind Notes
Exposure Category C
Windspeed Map Risk Categories 1-3 - 2023
Windspeed Map Risk Category 4 - 2023
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 48
- Structural Notes
Stamps required on all pages (SE and EE) SE/EE digital stamps on all PV pages, FL Statute, & PE Letter / Calcs. WS: 160mph. Exposure C. Please put stamped plans in one pdf not a folder because when you put in a folder it ruins the pe signatures. No more separate files for this AHJ.
Digitally Verified Signature
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,PV Breaker,Load Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
ESS Disconnecting Means. A disconnecting means shall be provided for all ungrounded conductors derived from an ESS. A disconnecting means shall be readily accessible and located within sight of the ESS. Remote Actuation. Where controls to activate the disconnecting means of an ESS are not located within sight of the system, the disconnecting means shall be capable of being locked in the open position, in accordance with 110.25, and the location of the controls shall be field marked on the disconnecting means. Busway. Where a dc busway system is installed, the disconnecting means shall be permitted to be incorporated into the busway. Notification. The disconnecting means shall be legibly marked in the field. The marking shall meet the requirements of 110.21(B) and shall include the following: (1) Nominal ESS voltage (2) Maximum available short-circuit current derived from the ESS (3) The associated clearing time or arc duration based on the available short-circuit current from the ESS and associated overcurrent protective devices if applicable (4) Date the calculation was performed Partitions and Distance. Where energy storage system input and output terminals are more than 1.5 m (5 ft) from connected equipment, or where the circuits from these terminals pass through a wall or partition, the installation shall comply with the following: (1) A disconnecting means shall be provided at the energy storage system end of the circuit. Fused disconnecting means or circuit breakers shall be permitted to be used. (2) A second disconnecting means located at the connected equipment shall be installed where the disconnecting means required by 706.7(E)(1) is not within sight of the connected equipment. (3) Where fused disconnecting means are used, the line terminals of the disconnecting means shall be connected toward the energy storage system terminals. (4) Disconnecting means shall be permitted to be installed in energy storage system enclosures where explosive atmospheres can exist if listed for hazardous locations. (5) Where the disconnecting means in (1) is not within sight of the disconnecting means in (2), placards or directories shall be installed at the locations of all disconnecting means indicating the location of all other disconnecting means. Location. Where ESS input and output terminals are more than 1.5 m (5 ft) from connected equipment, or where the circuits from these terminals pass through a wall or partition, overcurrent protection shall be provided at the ESS
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- Roof Plan
Rafters and attachments to be shown on the roof plan
- Roof Plan Notes
- Label Page
FLORIDA 2020 CAD BLOCK
- Custom Placards Required
- 0
- Placards Notes
- _ATTENTION INSTALL HOTLINE;_ _ DO NOT ALLOW INSTALL TO DEVIATE FROM PLANS SPECIFICALLY WITH ANY TYPE OF LAYOUT CHANGE, UNLESS ABSOLUTELY REQUIRED._
- Non Standard Revision Requirements
Cloud required on every revision
Ground mount
- Ground Mount Fencing Required
- No
- Ground Mount Notes
For setback requirements, or . Setback requirements vary by lot. The ground mounted array would need to be designed to meet or exceed the requirements in FBC Residential ch. 301. There is no freeze/thaw depth in this county. Footings shall be supported on undisturbed natural soils or engineered fill. If in a flood zone the elevation would need to be 1 foot over base flood elevation. For septic documentation, .