State of Idaho (DOPL) (ID)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL RESIDENTIAL CODE PARTS I, II, III AND IX
2020 IDAHO RESIDENTIAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2020 IDAHO ENERGY CONSERVATION CODE
2018 INTERNATIONAL EXISTING BUILDING CODE
2023 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 115
- Wind Notes
ASCE Wind Speed varies per elevation.
- Snow Load
- 999
- Snow Load Notes
ASCE Snow Load varies per elevation. Range: 20-56 lbs
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Please add a line to show "Roof Snow Load" or "Roof Live Load" to the structural calcs and/or the PE Letter, AHJ was specific on wording
- Minimum Ground On Roof
- #10
Electrical
- AC Disconnect Required
- Yes
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,Line Side Taps,Meter Adapter,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Site
* Buildings or structures supporting PV arrays shall have a Grounding Electrode System in compliance with NEC 250.50, 250.58 and 690.47 (A)
- Label Page
* Module spec sheets need to denote a National Laboratories (NRTL) mark * Provide manufacturer's doc of the type of PV wire that's being used, or denote the insulation type on the ELD to show compliance with NEC Chapter 3 * Provide Manufacturer's doc of the type of J-box(es) that are being used to show compliance with NEC 110.3 and 314.16 OR clarify tyoe, size and rating of the j-box(es) that will be used on the ELD
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Yes
- Ground Mount Notes
Clarify how the transition from PVC to EMT is being done in compliant with NEC 358.6, and 352.6. Clarify how transition will be compliant with NEC 250.96(A). No mesh netting required.