City of Ottawa (IL)

Illinois Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2020
Fire Code Version2018 Building Code
SolarAPP+ StatusTargeted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2020
Fire Code Version
2018 Building Code
Code List

2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2020 NATIONAL ELECTRICAL CODE 2014 ILLINOIS STATE PLUMBING CODE 1997 ILLINOIS STATE ACCESSIBILITY CODE 2018 INTERNATIONAL PROPERTY MAINTENANCE CODE 2018 INTERNATIONAL FIRE CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE CITY OF OTTAWA MUNICIPAL CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Targeted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,Derate
How Many Plansets Required
1
Revision Required
0
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
No
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
90
Snow Load
20
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

Standard

Minimum Ground On Roof
#10

Electrical

Allowed POI
Meter Adapter,Load Side Taps,PV Breaker,Line Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements
  1. Provide complete calculations including all dimensions on how the roof area was calculated or indicate a minimum 36” setback from the ridge.
  2. Provide manufacturer spec sheets for the proposed panels.
Electrical Diagram

ELECTRICAL (2017 National Electric Code as Amended)


  1. Tap conductors are permitted within the meter socket enclosures and service panelboard cabinets when the splices or taps do not fill the wiring space at any cross section to more than 75%. The typical 100-ampere meter socket does not have ample cabinet space for the installation of tap conductors. The alternative installation would include a new 100-ampere meter socket designated for supply side tap conductors that would include mounting studs capable of permitting the attachment of a listed wire lug suitable for supply side tap conductor terminations. (Article 312.8)
  2. Installation specifications for the piercing connectors shall be onsite for inspection.
  3. Any deficiencies in the Grounding Electrode System shall be corrected during this project.
  4. The licensed electrician shall be onsite at the time and date of the final inspection. Only trained personnel shall be available at the time of the final inspection to engage energized electrical equipment.

  

Electrical Diagram Notes

ELECTRICAL (2017 National Electric Code as Amended)


  1. Tap conductors are permitted within the meter socket enclosures and service panelboard cabinets when the splices or taps do not fill the wiring space at any cross section to more than 75%. The typical 100-ampere meter socket does not have ample cabinet space for the installation of tap conductors. The alternative installation would include a new 100-ampere meter socket designated for supply side tap conductors that would include mounting studs capable of permitting the attachment of a listed wire lug suitable for supply side tap conductor terminations. (Article 312.8)
  2. Installation specifications for the piercing connectors shall be onsite for inspection.
  3. Any deficiencies in the Grounding Electrode System shall be corrected during this project.
  4. The licensed electrician shall be onsite at the time and date of the final inspection. Only trained personnel shall be available at the time of the final inspection to engage energized electrical equipment.
Custom Placards Required
0
Non Standard Planset Requirements
N/A

Ground mount

Ground Mount Fencing Required
Mesh/Scrim