City of Yorkville (IL)

Illinois Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2017
Fire Code Version2018 Building Code
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2017
Fire Code Version
2018 Building Code
Code List

2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PROPERTY MAINTENANCE CODE 2018 INTERNATIONAL FIRE CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 EXISTING BUILDING CODE 2018 ILLINOIS STATE BUILDING CODE 2017 NATIONAL ELECTRIC CODE

IEBC Accepted
1
ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

How Many Plansets Required
1
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
0

Stamps

Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category B

Snow Load
25
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

107 MPH windspeed

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
Derates
Allowed POI
Line Side Taps,PV Breaker,Load Side Taps,Meter Adapter
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
1

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

ESS Elevation Detail Required
No

Plan set

Plan Set Requirements

BATTERY ENERGY STORAGE SYSTEMS (BESS)

Due to the potential for an uncontrollable fire related to Battery Energy Storage Systems, the following elements are required for installation of such systems within or outside of a structure within the City of Yorkville IL:


1. Location - Battery energy storage systems shall be located either outside of the residential structure or within the garage area. These systems shall not be located within the living area or basement of the home.


2. Emergency Egress - Battery energy storage systems shall not be located within an egress route and shall not interfere with the safe evacuation of the residents from the structure.


3. Wall Mounting - Battery energy storage systems may be wall mounted in the garage on the exterior walls only, and only IF the walls are constructed of a minimum of 2x6 framing materials.


4. Floor mounted - Battery energy storage systems may be mounted on the floors of garages.


5. Location in garage - Whether mounted on a wall or on the floor, the batteries may not be located within 10 ft. of any egress door or path to allow for safe egress from the structure.


6. Fire rating - Walls and ceilings surrounding the batteries shall have a 2-hour fire rating for all areas above and within 4ft of the dimensions of the batteries. This rating is achieved by two layers of 5/8" Type X drywall with staggered seams. All seams must be fire taped and sealed. The ceiling above the battery must maintain this fire rating for 4' on each side of the battery.


7. Heat detection - In garage installations a means of heat detection will be provided and shall be interconnected with the home smoke alarm system for emergency notification of the occupants.


8. Required Signage - Approved signage shall be provided on doors or in locations near entrances to battery storage areas that shall notify them of the existence of energy battery systems, energized electrical circuits, and the location of the battery storage disconnecting means if it is not within sight of the main service disconnecting

means.


9. Vehicle Impact Protection- Where battery storage systems are subject to impact by a motor vehicle, vehicle impact protection shall be provided in accordance with the provisions of IFC 312 or other approved means.

These requirements are not to be considered all-inclusive and are dependent upon the design and location of the energy storage system. This document shall be considered a living document and shall be amended as technology and/or regulatory changes occur.

Electrical Diagram

Standard

Custom Placards Required
0
Non Standard Planset Requirements
N/A

Ground mount

Ground Mount Fencing Required
Mesh/Scrim
Ground Mount Notes

YES BUT A SITE PLAN SHOWING SETBACKS MUST BE SUBMITTED

Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the City of Yorkville (IL) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.