Town of Charlton (MA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
10TH EDITION OF THE MA STATE BUILDING CODE 780
2021 INTERNATIONAL BUILDING CODE W/780 CMR
2021 INTERNATIONAL RESIDENTIAL CODE W/780 CMR
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL FIRE CODE
2023 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 2
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Ee Stamp Notes
- No EE required
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 125
- Wind Notes
Exposure Category B
- Snow Load
- 50
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Engineering letter to include. * Span, Spacing, Species and Span break information (knee walls, collar ties). * Any snow sliding / drifting into valleys affected by new panels. * Snow impact loads on structures and accessory structures below new Panels (Decks, Porches etc.). CALCULATION MUST BE SHOWN * Copy of onsite survey report being sent to engineer.
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Meter Adapter,Load Side Taps,Line Side Taps,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 1
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
***All designs in this AHJ must meet all requirements listed on AHJ solar permit checklist Charlton Requirements.pdf or otherwise will receive rejection***
- Include copies of specsheets for ALL equipment including mounting hardware and jbox
- Photos Required: All full sides of the house (minimum 4)
- Attic interior NOTE: If attic is non accessible, include a photo of site auditor measuring the rafter with a probe and it's dimension. Include measurements of rafter depth, span, spacing, and any span breaks
- Edge of roof showing number of layers of shingles, if applicable
- Copy of site report being sent to PE
- Roof Plan
* Condition and Age of roof covering and condition should be noted on plans * Porches, decks, or any attached or detached structures that could be affected by new solar panel installation should be drawn and labeled on plans. All roofs should be labeled on plans. * Snow guard required. Call out installation on plans.
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim