City of Brigham (UT)
Codes
- NEC Code Version
- 2017
- Fire Code Version
- 2018 Building Code
- Code List
2021 INTERNATIONAL BUILDING CODE 2021 INTERNATIONAL RESIDENTIAL CODE 2021 INTERNATIONAL MECHANICAL CODE 2021 INTERNATIONAL PLUMBING CODE 2021 INTERNATIONAL FUEL GAS CODE 2021 INTERNATIONAL ENERGY CONSERVATION CODE 2021 INTERNATIONAL EXISTING BUILDING CODE 2021 INTERNATIONAL SWIMMING POOL AND SPA CODE 2020 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 1
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category C
- Snow Load
- 43
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
#### **SNOW:** **Base ground load: 43 PSF** The ground snow load must be calculated in accordance with Section 1608.1.2 of the Utah Amended Code (Item 43) with regional snow load factors compliant with Table 1608.1.2(a). ** WIND: ** **Speed: 90 mph with 120 MPH 3 second wind gust. ** **Typical Exposure: “C” ** ** SEISMIC:** **Ground Motions: For specific acceleration values see the USGS National Seismic Hazard Maps.** Seismic Design Category: Site specific (per IBC 1613.3.5.1 Table 1613.3.5 (1)). "D" is typical **IBC: 2015** **IRC: 2015** **IECC: 2015** ** ** **ENGINEERING STAMP** **Plans must be wet stamped and signed by the engineer, copies may be denied. The engineering must be site specific.**
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Load Side Taps,Line Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Utah does not want single panel arrays with railless systems. Please have layout changed if this happens
- Attachment Detail
No single panel arrays with railless systems
- Electrical Diagram
MPU
- Clearly specify on the line diagram the exact model number of the service panel you are going to install and provide manufacturer specification sheets
- The line diagram must be drawn correctly based on the type of new service panel that will be installed.
- New service panel MUST be a type with only ONE MAIN breaker that shuts off all other breakers.
- The new service panel CANNOT be a type which has additional breaker slots fed directly from the utility meter (i.e., cannot install a “hot bus” service panel per the 2020 NEC)
- Label Page
- Label Page Notes
All Jobs [A sign with the exact wording “Rapid Shutdown Switch for Solar PV System” will be provided next to the rapid shutdown disconnect for this system]
- Custom Placards Required
- 0
- Non Standard Planset Requirements
- Single Line Diagram
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim