BHE - Black Hills Energy
Net metering & export
- Net Metering Allowed
- 1
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 0
- Allows Standby
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 2
- Line Taps Allowed
- 1
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Percentage
- Offset Value
- 200
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- System Offset Notes
120% offset maximum: The proposed PV system shall be sized to supply no more than 120 percent of the customer's average annual electricity consumption (measured in kWh) at that site
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Situational
- Production Meter Criteria
Effective 4.01.2025: Systems sized 10 kW AC and Under do NOT require a production meter; however, customers may choose to install a production meter at their own cost.
Projects over 10 kW AC require a production meter
- Production Meter Position
- Inv-PM-Disco-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Allowed Meter Adapter
- Tesla Backup Switch,ConnectDER
Plans & docs
- SLD Reqs
Production Meter Requirements
- Systems sized at 10 kW AC and Under do NOT require a production meter
- Projects over 10 kW AC require a production meter
- Both the production meter and utility meter socket must be rated at 200A, this must be shown on plans (including the one-line diagram)
- Only one Production Meter per address, if there is an existing PV meter, new AND existing production must run through that meter.
- Production Meter needs to be MILBANK U4801-XL-5T9 - 200A lever bypass meters & #6 AWG wire is required on the line and load side of the PV meter <<<<<<<< READ THIS NOTE!!!
Utility Meter Requirements
- Both the production meter and utility meter socket must be rated at 200A - Label as (E) or (N) "UTILITY METER (200A) (1PH, 3-W, 240V)", this must be shown on plans (including the one-line diagram)
- See the files section to determine if the existing utility meter is a 100A or 200A. If it is 100A, We need to upgrade it to a (N)200A <<READ THIS NOTE!!!
- THE UTILITY METER NEEDS TO BE CALLED OUT AS (N)200A or (E)200A. <<READ THIS NOTE!!!

SLD/3LD Requirements
- 3LD and SLD are required
- ONLY IF PM IS REQUIRED: SE3800H-USRGM inverter will be required to have a 35A PV breaker & #6 AWG wire from PM to POI.
- If PM is NOT required, SE3800 will use standard wire and breaker size (#10 gauge and 20A breaker)
- Install Reqs
The system must be permanently installed or attached to a building, foundation or permanent structure. Portable or mobile systems are not allowed.
- Placards
- AC Disco label must read "Customer Generation AC Disconnect"
- Production meter label must read "Customer Generation Production Meter/ Open AC Disconnect Before Removing Meter"
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Electrical Diagram Notes
- Website
- link
- Phone
- 719.546.6472 Devin