CELD - Chicopee Electric Light
Net Metering Allowed1
NEM TypeAnnual
Line Taps Allowed0
Load Taps Allowed0
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Other
- Net Excess Generation Notes
The kilowatt hours produced by the generator will be credited against the corresponding On/Off peak usage at the rate for that customer-generator’s current class of service. If the customer produces more energy than it uses for the month, the customer will be credited on its bill for the excess generation at the full retail rate and the credit will be carried over to the following billing period.
- Rebates Offered
- 0
- Deregulated
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Position
- Inv-PM-Disco-POI
- Production Meter Labeling
- Production Meter
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
- Production meter to be labeled as "CEL owned production meter"
- SLD Reqs
Relay Meter Orientation = Over/Under
- Production meter wired with the bottom facing the Line/Utility and the Top facing Generation (PV).
- Production meter to be labeled as "CEL owned production meter"
- Electric Service Reqs
Requirements vary by location and are addressed during the Preliminary Review Process
- Website
- link
- Phone
- (413) 598-8311
Other details
- Restrict Inspection
- 0
- Revision Required
- 0
- Mod Swap Requires Planset
- 1
- Address ID
- 126670
- Express Planset Eligible
- No