NG - National Grid (MA)

Massachusetts Utility Interconnection & net metering rules

Spot something wrong?

Tariffs and interconnection rules move often. If something here is out of date or missing, tell us and we'll fix it.

Report a correction
Net Metering AllowedYes
NEM TypeMonthly
Supply Side Taps AllowedYes
Line Taps AllowedYes
Load Taps AllowedYes
AC Disconnect RequiredYes

Net metering & export

Net Metering Allowed
Yes
NEM Type
Monthly
TOU Utility
No
Post Solar Billing Method
Net Metering
Solar Export Type
N/A
Net Excess Generation Notes
  • Excess generation at the end of each month is credited at the applicable retail electricity rate and rolled forward to future bills as a dollar credit. This credit rolls forward indefinitely to future bills but cannot be "cashed out".
Rebates Offered
Yes
Deregulated
Yes
Allows Standby
Yes

Interconnection & taps

Approval Req To Install
Yes
Supply Side Taps Allowed
Yes
Line Taps Allowed
Yes
Load Taps Allowed
Yes
Tap Criteria
  • Cannot be in same compartment as utility meter.
  • (2) AC disconnects are required. Inv > Non-fused Disco (outside) > Fused Disco (inside, if necessary) > POI
Automatic Transformer Upgrade Size
0
Meter Aggregation Allowed
Yes

System size & offset

System Size Restrictions
25
System Size Restriction Type
AC kW
System Size Battery Included
No
System Size Includes Existing Systems
No
Offset Type
No Restrictions
Offset Value
0
Offset Calculation Period
0
Industry Standard Watts Sqft
2
Utility Specific Adjustments

Please keep system size under 15 kW AC whenever possible.

For example:

  • Please use mix of 7.6KVA and 5.7KVA to be under 15KW AC rather than using two 7.6KVAs. This will avoid Level 2 application and reduce approval times.

Curtailment Requirements

  • National Grid allows system curtailment to avoid transformer upgrades and group studies
  • Approved curtailment systems: Tesla Gateway, Enphase IQ, and Generac PWRcell
  • Update all documents to show the system curtailed to 15 kW AC export
  • Add a label showing aggregate AC kW/kVA ratings
  • Show both total system size and curtailed system size
  • Show internal DB protective device settings for inverters (see Tables 7.6.11.1-1 & 7.6.11.1-2, Page 33 in ESB 756)
  • Provide a curtailment letter on manufacturer letterhead if the system is larger than the proposed export, including the model number of the Smart Hub/Gateway and the proposed system output (curtailed value)
Inverter Oversize Restrictions
Yes
System Size Justification
Load Justification
System Offset Notes


Metering & disconnect

Production Meter Required
Situational
Production Meter Criteria

Production Meter (SMART meter)

  • Required for: Cash, Loan, Aura, Aura+
  • Not required for: Lease projects
  • Wire inverter on bottom side and utility on top side
  • Only 1 production meter per project
  • Second meter allowed only if 12 months have passed since existing system PTO
Production Meter Position
Inv-Disco-PM-POI
Production Meter Labeling
Production Meter
AC Disconnect Required
Yes
AC Disconnect Labeling
Accessible and Lockable AC Disconnect
Meter Spot Required
No
Allowed Meter Adapter
None

Plans & docs

Electric Service Reqs
  • Meter relocation is required if the utility meter is located indoors or inside any cabinet
  • Single Meter - Center of meter must be between 30 and 60 inches
  • Multi Meter - Center of meter must be between 36 and 60 inches
Placards
  • Unit designation labels are required for the meter sockets at the premise (Example; Unit 1, Apt 1, etc)
Electrical Stamp Required
Yes
Equipment Approvals
Other
Meter Num Req SLD 3LD
No
ESID Num Req SLD 3LD
No
Site Plan Notes


Label Page Notes


Cover Page Notes


Electrical Diagram Notes

Battery [STORAGE CHARGING CAPABILITY: GENERATION ONLY STORAGE DISCHARGING CHARACTERISTICS: ON-SITE LOAD ONLY]

Website
link
Phone
(800) 322-3223

Other details

Revision Required
Yes
Mod Swap Requires Planset
Yes