Xcel Energy (MN)
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 0
- Deregulated
- 0
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Tap Criteria
- For Load/Line side taps: If system less than 10kW DC = Inv > 60A Fused Disco > POI. The AC disconnect is NOT the utility AC disconnect. Do not include the note.
- If system more than 40kW DC = Inv > Non-fused Disco > top of PM > 60A Fused Disco > POI. Non-fused disconnect is the utility AC disconnect. Label and note accordingly.
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 40
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 1
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
40 kW AC max
Systems over 40 kW will have a 120% offset requirement
Metering & disconnect
- Production Meter Required
- Situational
- Production Meter Criteria
PM is only required on Systems 40kw or larger
- Production Meter Position
- Inv-Disco-PM-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
Plans & docs
- Site Plan Reqs
Approved Planset: Lucky Amedu (461924) ()
Xcel MN Checklist: CHECKLIST
SITE PLAN SHOULD HAVE ALL EQUIPMENT LABELED PROPRERLY SHOWING ELECTICAL PHASING AND VOLTAGE EX: 1-PHASE 240V
CROSS ROAD SHOULD BE SHOWN ON SITE PLAN
Electrical Component Locations
- SEPERATE BLOCKS FOR UTILITY METER AND MSP SHOULD BE UTILIZED ON SITE PLAN
- AC DISCONNECT SHOULD BE WITHIN 10FT OF UM, DISTANCE SHOULD BE NOTATED ON TLD
- PLACARD REQUIRED IF EQUIPMENT IS NOT WITHIN 10FT OF UTILITY METER
- OVER HEAD LINES SHOULD HAVE PROPER 3FT CLEARANCE FROM MAST
GROUND MOUNT PROJECTS
- An access road is required to all Xcel Energy equipment, including production metering and AC disconnects. The width of this road shall be indicated and cannot be less than 12’ wide. It shall show the route from a public road to the Xcel Energy equipment. Include sufficient space of turn‐ around for ease of accessibility.
- SLD Reqs
All requirements are listed below.
- AC DISCONNECT SHOULD BE LABELED AS "UTILITY AS DISCONNECT VISIBLE, LOCKABLE, READILY ACCESSIBLE "
- UTILITY METER PHASE AND VOLTAGE SHOULD BE ADDED TO TLD EX: 1-PHASE, 3 WIRE, 240V or 3-PHASE, 4 WIRE 208V
- Leader pointing to inverter "RPA CONNECTION"
- ESS SHOULD PROVIDE CONFIGURATION MODE EX: SELF CONSUMPTION
- A production Meter is ONLY required for applications that are 40kW or greater The PV production meter will be required to have the PV generation wired to the line side terminals. Please indicate the LINE SIDE and LOAD SIDE of the PV production meter on the line diagram
ESS PROJECTS
For energy storage systems: the configuration being applied for shall be clearly indicated. Please note the correct alphanumeric configuration out of the options listed in Appendix B of the technical specification manual.
See FILES SECTION "MN-ESS Appendix B.pdf"
M3 - IF ESS, a declaration of storage is required. Please upload a declaration of storage document to Salesforce from Appendix C of the Technical Specifications Manual; be sure to select the form that matches the alphanumeric configuration that will be noted on one-line.
See FILES SECTION "MN-ESS Appendix C.pdf"
#NFZ_ALL#
- Electric Service Reqs
UTILITY METER MUST MEASURE 12''X18'' TO AVOID METER UPGRADE. METER UPGRADE IF DIMENSIONS ARE LESS THAN 12''X18''. THE NEW METER SHOULD BE MILBANK WITH LEVER BYPASS. LINE SIDE TAP VIA MILBANK K4977 INT LUG KIT IS ALLOWED IN AN EXISTING OR NEW MILBANK METER.
- Install Reqs
- Placards
- Electrical Stamp Required
- 0
- Equipment Approvals
- California Energy Commission
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Site Plan Notes
All Jobs [24/7 UNESCORTED KEYLESS ACCESS SHALL BEPROVIDED TO ALL XCEL ENERGY EQUIPMENT // UTILITY METER AND UTILITY AC DISCONNECT MUST BE WITHIN 10' OF ONE ANOTHER AND READILY ACCESSIBLE]
Overhead [No overhead clearance issues]
Underground [No overhead service lines exist]
- Label Page Notes
- Electrical Diagram Notes
All Jobs [-PHOTOVOLTAIC SYSTEM CONNECTED YELLOW WITH BLACK LETTERING PLACARD TO BE LOCATED ON MAIN BILLING METER // -UTILITY PV AC DSICONNECT YELLOW AND BLACK LETTERING PLACARD TO BE LOCATED ON UTILITY PV AC DISCONNECT// -DER EQUIPMENT IS SINGLE PHASE, 240V AND UL LISTED // -AC DISCONNECT IS WITHIN 10FT OF UTILITY METER // -UTILITY ACCOUNT#: ###########]
- Website
- link
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Express Planset Eligible
- No