City of Washington (NC)
Net Metering Allowed1
Line Taps Allowed0
Load Taps Allowed0
AC Disconnect RequiredYes
Net metering & export
- Net Metering Allowed
- 1
- TOU Utility
- 1
- Post Solar Billing Method
- Feed-in-Tariff
- Solar Export Type
- Fixed kWh
- Solar Export Rate
- 0.02
- Solar Export Value Notes
- For non-TOU customers the amount of credit for all energy delivered to the City will be $0.0232 per kWhr. In no case shall the energy delivered to the City be less than zero. If the meter on
- Rebates Offered
- 0
- Deregulated
- 1
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 10
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Residential PV systems shall be limited to 10 kW maximum ac output. Special provision may be negotiated for larger PV installations on an independent connection basis. PV systems larger than 10 kW maximum ac output capacity may require special review, additional testing and special interconnection facilities.
- Offset Calc Tool
- Historical Usage
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Position
- Inv-Disco-PM-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
Plans & docs
- Site Plan Reqs
Standard - pending example from utility
- SLD Reqs
Standard - pending example from utility
- Electric Service Reqs
Production Meter Required:
- All PV installations must be connected to the City electric system through a separate PV interconnection meter. See attached installation illustration and single-line diagram
Disconnect Required:
- Must have a service disconnect installed adjavent to the meter.
- Disconnect shall be fully accessible to the utility
- Disconnect shall include provisions for locking in the open position
- Disconnect shall be labeled in accordance with NEC 705.10
All PV systems shall be non-islanding
All PV systems shall operate within the range of 0.90 lead to 0.90 lag power factor.
Conductors and isolation switch shall be sizedx in accordance with the requirement of the NEC with a minimum rating of 100A
- Placards
AC Disconnect
- Shall be labeled "SOLAR PANEL ISOLATION SWITCH".
- Electrical Stamp Required
- 0
- Equipment Approvals
- California Energy Commission
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Website
- link