Easley Combined Utilities
Net metering & export
- Net Metering Allowed
- 1
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Fixed kWh
- Solar Export Rate
- 0.04
- Solar Export Value Notes
- "On-Peak Energy 4.244 ¢/kWh Off-Peak Energy 2.755 ¢/kWh"
- Net Excess Generation Notes
Excess generation will be credited under the Schedule A on a monthly basis. Any generation accumlated at the EOY will be paid out to the customer.
- Rebates Offered
- 0
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 20
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Max. 20KW or 90% of service rating whichever is less.
- Offset Calc Tool
- N/A
Metering & disconnect
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Panels, inverters, disconnect switch and connection point. We do not require a production meter. We encourage back feeding a breaker in the customer’s panelboard. Pierce connection in the meter base will not be allowed. Only meter bases designed for two sets of service wires can have the solar system connected in the meter base.
- Electric Service Reqs
Warning: Cut meter seals are considered tampering and may incur a $500.00 charge to the customer. Seals can only be removed with an ECU employee present.
- Install Reqs
Customer shall install a manual disconnect switch of the visible load break type toprovide a separation point between the AC power output of the CRG system and any Customerwiring connected to Utility’s electric system such that back feed from the CRG system toUtility’s electric system cannot occur when the switch is in the open position. The manual disconnect switch shall be mounted separate from the meter socket on an exterior surface adjacent to the meter. The switch shall be readily accessible to Utility and capable of being locked in the open position with a Utility padlock. When locked and tagged in the open positionby Utility, this switch will be under the control of Utility.
- Website
- link
- Phone
- (864) 859-4013
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Address ID
- 155175
- Express Planset Eligible
- Yes