Orangeburg DPU
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 1
- Post Solar Billing Method
- Export Rate
- Solar Export Type
- Fixed kWh
- Solar Export Rate
- 0.07
- Net Excess Generation Notes
Energy Charges shall be based on the applicable tariff Power Supply Charge plus applicable Distribution Charge applied to the kilowatt-hours purchased from the Department for the bill month. Energy Credits shall be based on the current Rate 2I Power Supply Fuel Charge applied to the kilowatt-hours delivered to the Department for the bill month. The net Energy Charge for any bill month shall be the Energy Charges for the bill month minus the Energy Credits for the bill month. For any bill month during which the net Energy Charges are a credit, the respective Energy Charges for the month shall be zero. Credits shall not offset the Service Charge or the Demand Charge.
- Rebates Offered
- 0
- Deregulated
- 0
- Allows Standby
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 20
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- PV Watts
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
DPU will require:
1. Overcurrent Protection and Ratings for the Utility Required AC System Disconnect Switch,
2. Rapid Shutdown Compliance with 2017 NEC.
3. All Equipment Engineering Data for PV Modules, Inverter (UL 1741), Batteries (if used), and Disconnect Fuses or Circuit Breakers.
4. Method of connection to utility.
5. Proper Labeling of Solar/PV equipment and UL Listing of Switches and other equipment.
IF the One-Line Diagram is not properly and adequately provided, DPU will not connect.
On the Site Plan, the utility required AC Disconnect switch shall be shown located in the immediate vicinity as the utility meter, and shall be readily accessible, meaning not installed inside a fenced area, or other place that utility employees can’t quickly access the disconnecting switch.
All conductors shall be adequately protected against short circuits and overcurrents per the NEC and a decent One-Line diagram will reflect all that. Please refer to SLD sample
- Install Reqs
Utility Inspection Required: Yes
(Interconnection Requirements - Page 6, Section 5.2) A manual load-break disconnect switch or safety switch with a clear
visible indication of switch position between the EPS and the Generator. The switch must have pad lock provisions for locking in the open position. The switch must be visible to, and accessible to the Department personnel. The switch must be in close proximity, and visible from, the Customer’s point of electrical interconnection with the Department’s EPS. The switch must be labeled “Generator Disconnect Switch”. The
switch may isolate the Generator system and its associated load from the EPS or disconnect only the Generator from the EPS. After Install: Please do not close, or allow your electrician / installer to close, (place in the “on” position) the lockable disconnect switch until DPU has conducted its safety inspection of the installation.
- Placards
The AC disconnect must be labeled “Generator Disconnect Switch”
- Electrical Stamp Required
- 1
- Equipment Approvals
- California Energy Commission
- Website
- link
- Phone
- (803) 268-4204