FELPS - Floresville Electric Light & Power System
Net metering & export
- Net Metering Allowed
- 1
- TOU Utility
- 1
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 0
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Tap Criteria
Lineside interconnection is not allowed, it has to be on the load side on a dedicated breaker (Piecing tap not allowed).
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 50
- System Size Restriction Type
- DC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
UP to 50kW
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Position
- Inv-Disco-PM-POI
- Production Meter Labeling
- Production Meter
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
- Meter Socket (required)
- PV > INV > Disco > PM > MSP
- No interior sub POI allowed
- If POI is on the FELP pole (W/ transformer), PV Equipment required to be installed on rack 6ft away.
- If it's on the customer-owned pole, can attach to the pole.
- Electric Service Reqs
Note- 1: The customer shall provide and install a manual load break switch that provides a clear indication of the switch position at the Point of Interconnection to provide separation between the FELPS electrical system and the customer's electrical generation system. The connections shall be labeled FELPS and Solar both inside and outside of the box identifying where the connection comes from. The location of the disconnect switch must be approved by FELPS. The disconnect switch shall be easily visible, mounted separately from metering equipment, readily accessible to FELPS personnel at all times, and capable of being locked in the open position with a FELPS padlock.
Note-2: The location of the fused disconnect or breaker boxes must be approved by FELPS. The disconnect or breaker boxes shall be easily visible, readily accessible to FELPS personnel at all times, and capable of being locked open in a way that would protect FELPS personnel from accidental closing and re-energizing of the system while work is being done by FELPS personnel in the area.
- Website
- link
- Phone
- (830) 216-7000