SWEPCO - Southwestern Electric Power Co. (TX)
Net Metering Allowed0
NEM TypeMonthly
Line Taps Allowed1
Load Taps Allowed0
Net metering & export
- Net Metering Allowed
- 0
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Export Rate
- Net Excess Generation Notes
SWEPCo payback is at avoided cost any kwh’s sent back to the grid is paid at avoided cost - about 2.3 cents a kWh
- Rebates Offered
- 0
- Deregulated
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 2
- Line Taps Allowed
- 1
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Meter Spot Process
https://www.swepco.com/account/service/upgrade/UpgradeHomeService.aspx
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
The disconnect switch should be located within 6’ of the meter. If it is not possible to do so, we require a permanent plaque installed at the meter base stating the specific location of the switch. This will have to be in place before we issue a meter change order.
- SLD Reqs
Taps
- line side tap conductors must end in a breaker or fuses not in mlo lugs in the panel.
Battery
- AC disconnect must be placed between the utility meter and the Tesla gateway
- Electric Service Reqs
We require a visual open point, preferably a blade style, for the disconnect switch. We do not accept breakers as these would have to be physically removed to be a visual open point.
- Website
- link
- Phone
- 903-234-7333
Other details
- Restrict Inspection
- 0
- Address ID
- 108148
- Express Planset Eligible
- Yes