City of St. George
Net metering & export
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- No
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 0
- System Size Restriction Type
- No Restrictions
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Size Justification
- Load Justification
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Position
- Inv-PM-Disco-POI
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Solar electric modules
Inverter
Batteries (if applicable)
Lockable Disconnect Switch
Utility required production meter
Point of connection with the utility system
All electrical equipment specifications and calculations must be shown on the oneāline. Any signs/labels should be shown with their respective calculated values on the oneāline. The installation address, current account number at that address, and the installerās name and telephone number must also be included.
All datasheets for the proposed equipment (solar panels, inverters, cable, etcā¦) must be included in the application as well as a structural load design and letter from a structural engineer licensed in the State of Utah.
If the proposed system includes a battery backup or generator backup, a detailed wiring diagram and shop drawings of all equipment shall be submitted with the application.
For a 6000 Inverter please use a 40A 2P Breaker. There is a shortage of 35A Breakers - 11.23.20
- Electric Service Reqs
Contact the St. George City at to request a copy of your energy use history
- Placards
Labels shall be engraved plastic where exposed to sunlight. Handwritten marker pen labeling is _not_ allowed. The Label Sheet must include the location of the labels. Labels shall be read background with white lettering. Lettering must be at least 1/4" in height. The following labels must be provided:
Single Source Systems Only
WARNING: SINGLE 120 VOLT SUPPLY, DO NOT CONNECT MULTI-WIRE BRANCH CIRCUITS
AC & DC Disconnects
DC: " PHOTOVOLTAIC SYSTEM DC DISCONNECT"
AC: "PHOTOVOLTAIC SYSTEM AC DISCONNECT"
WARNING: ELECTRIC SHOCK HAZARD. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION
DC DISCONNECTS - This section must be completed if a main inverter system is being installed.
Maximum System Voltage
Maximum circuit current
Maximum rated output current of the charge controller (if used)
At the interactive points of interconnection, usually the main service
Rated AC output current
Normal operating AC voltage
Inverter
Inverter - Must be a reflective sticker
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
At the electrical service and at the photovoltaic inverter (if not located in the same location)
A directory providing the location of the service disconnect means and the photovoltaic system disconnecting means. _
Back-fed panel boards, inverter output OCPD
"WARNING: INVERTER OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE" _This can be a sticker if inside breaker panel and not exposed to sunlight.
Main Service Panel
For PV Systems that shutdown the Array and conductors leaving the array. - Placard must be yellow **(Example is shown on PG 5 of the Net Metering Application below.)
"SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN"
"TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY"
"WARNING: MULTIPLE SOURCES OF POWER. A PV SYSTEM IS PRESENT. DISCONNECT ALL POWER SOURCES BEFORE SERVICING."
Conduit, Raceway's, Enclosures
On Conduit, raceways, enclosures: Mark every 10', at turns, above or below penetrations:
"CAUTION: SOLAR CIRCUIT"
- Site Plan Notes
Utility must have 24 hr access to disco and PM
- Rate Schedule Link
- link
- Website
- link
- Phone
- (435) 627ā4095
Other details
- Restrict Inspection
- 0
- Address ID
- 108117
- Express Planset Eligible
- No